Main Parameters
|
Rated Parameters of the Power Supply Under Test |
AC230V*3+ AC230V*3 50~60Hz |
|---|---|
|
Rated Load Power |
12kW (total rated power of dual circuits) |
|
Load Characteristics |
Resistive Load |
|
Load Connection Mode |
Daelta connection |
|
Three-phase Balance |
≤3% |
|
Load Regulation Capability |
Single source 0-12kW, dual source 0-6kW ; Minimum step 100W |
|
Load Protection Function |
Over-temperature protection, overvoltage protection, overcurrent protection, etc |
|
Load Control |
Manual load step switching via circuit breakers |
|
Load Working Mode |
Continuous Operation |
|
Cooling Method |
Air Cooling |
|
Measurement and Control Function |
Measuring the voltage, current, power, frequency, etc. of the power supply under test |
|
Load expansion |
Parallel expansion of 1+N load units |
|
Operating Environment |
Indoor type |
|
Appearance Dimensions |
485×220×700mm (W×H×D, Enclosure) |
|
Operating Ambient Temperature |
Temperature Range -10℃ to +55℃ |
|
Weight |
40kg |
|
Operating Altitude |
≤2000 Meters |
|
Installation and Transportation |
Rack-mounted design with a stainless steel U-handle |
|
Insulation Class |
IP21 |
|
Product Application Scope |
Suitable for data center power supply testing and air conditioning system testinga |
Features
-
Supports dual A/B power input and reproduces the load of redundant server power supplies in a data center. When both feeds are live the load splits 50/50; if one feed fails, the full load transfers to the live feed within milliseconds.
Rated at 10 kW with staged manual loading through independent industrial circuit breakers on the front panel, in steps down to 100 W. Switching is fully mechanical — no software setup, no communication link.
Independent front-panel digital ammeters show live current on each feed, so per-feed current and load balance can be read without a clamp meter.
High-precision alloy resistor tubes with a low temperature coefficient and low impedance, housed in stainless steel sheaths, for stable heat output through 24/7 full-load operation.
Standard 19-inch 5U rack-mount all-metal chassis with front pull handles and rack ears. EC fans with front-intake/rear-exhaust airflow follow data center hot/cold aisles and limit hot-air recirculation into neighboring equipment.
Overvoltage, overcurrent and over-temperature shutoff, fan-fault interlock, and phase-loss/imbalance protection. A blocked intake or an electrical fault triggers an automatic load trip and alarm, so the unit can run unattended safely.
Rack Mounted Doual Source Load Bank Customization Services
Rated power and minimum step customization
Rated power (6–12kW) and minimum step (100W/200W/500W) customizable; optional precision resistors for ±3% loading accuracy.
Dual-feed power split customization
A/B ratio and transfer logic configurable; standard 50/50 split and 100% backup takeover, plus non-symmetrical split (e.g., 70/30), independent per-feed control, custom delay.
Communication interface customization
The standard unit has no communication interface. A host-controller connection can be added as a project-specific custom option.
Input and connector
customization
Terminal blocks are available for both single-phase and three-phase AC input and can be configured to match your specific connection requirements.
Enclosure form and structure customization
The rack height (3U / 4U / 5U), chassis depth, and powder-coat finish are customizable, and OEM front-panel silk-screen branding can be added to match your brand identity.
Airflow and protection customization
Exhaust direction and low-noise EC fans adjustable; over-temperature trip, fan interlock, transfer indicators, and E-Stop .
FAQ
The equipment features a built-in dual-power automatic switching controller and PLC control logic. With dual power supplies operating normally, the total load is automatically distributed evenly between Port A and Port B at a 50%-50% ratio. If one power supply suddenly fails, the entire load automatically switches to the normal power supply circuit within milliseconds, requiring no manual intervention. When power is restored to the failed circuit, the PLC controls the load to be redistributed evenly between the two circuits. This seamless switching ensures the continuity of testing for the backup power supply and dual-power system.
Supports 1+N parallel expansion mode; a single host computer (host computer) can control up to 800 load banks of various types via our remote control software. Different models of load banks are also compatible for joint control. Networking methods support wired and wireless networking. Wired networking can be cascaded via network cables through the device's built-in two communication interfaces. Wireless networking allows load banks to be grouped and connected to a wireless router, and then the host computer connects to the wireless router for centralized management of all connected load banks.
Our dual-circuit air-cooled load cell is designed with a loading accuracy of ±3% and a three-phase current balance of ≤3%, which is better than the average level of conventional resistive load cells.
-
When a warning (such as overvoltage, undervoltage, or overcurrent alarm) is triggered, the equipment will continue operating as a warning only.
-
When an error (such as overvoltage, overcurrent, emergency stop, communication interruption, or overtemperature fault) is triggered, the equipment will trigger a protective shutdown. An alarm will sound, and the alarm information will be simultaneously pushed to the host computer (control computer) to prompt manual intervention.
-
The fault status will be latched. After the fault is cleared, the equipment can be manually reset by clicking the "Clear Alarm" button on the HMI's STATUS interface to resume normal operation.
To ensure efficient heat dissipation, especially for air-cooled load cells, there should be no obstructions within 1 meter in front of the front and side air inlets, and no obstacles or other equipment within 5 meters of the air outlets. This will prevent hot air recirculation and overheating of the equipment. After the load is unloaded, the fan will continue to run for a period of time according to the program settings to remove residual heat from the equipment (especially resistors). It will only stop when the temperature drops to a safe threshold. Do not turn off the power before the fan stops.
Local/remote control modes can be easily operated via the local touchscreen HMI. On the Home screen, clicking the green "local" button switches to local operation, while clicking the green "remote" button switches to remote operation from the host computer.
In remote control mode, multiple units can be centrally loaded and unloaded, and voltage, current, power, frequency, imbalance, etc., can be monitored in real time. Data is automatically recorded to the host computer and can be exported as a CSV table for subsequent analysis, meeting the needs of large-scale system-level testing scenarios.
The resistance tube is made of U-shaped nickel-chromium alloy, and the outer shell is made of stainless steel alloy tube resistant to salt spray and acids and alkalis. It has the characteristics of low temperature coefficient and stable impedance, which can ensure consistent performance during long-term continuous operation.
The product has an insulation class of F and is equipped with dual temperature protection for over-temperature of the resistance area and the electrical control area. With the stepless speed-regulating air cooling system, it can support long-term continuous operation.
-
Check if there is undervoltage on either of the tested power supplies. If the voltage value is lower than the undervoltage alarm threshold (factory default 200V), it will affect the switching logic.
-
Check the meter communication status. If the meter communication is interrupted for more than 16 seconds, it will cause abnormal voltage detection, thus preventing automatic switching from being triggered.
This load cell is designed for indoor use, with an operating temperature range of -10℃ to +55℃ and an altitude not exceeding 2000 meters. It should be used and stored in a dry, well-ventilated indoor environment, avoiding water exposure, moisture, and extreme temperatures. Although the casing is resistant to salt spray and acid/alkali corrosion, long-term storage in such environments is still recommended.
