21kW-35kW Dual Source Air-Cooled Load Bank

The Batterlution 21kW dual-power air-cooled load cell has a rated power of 21kW and a minimum step power of 1kW. The load power supply uses U-shaped NiCr alloy resistors and is cooled by a steplessly variable speed fan (the PLC program automatically adjusts the fan speed based on the detected temperature), balancing heat dissipation and energy saving, making it suitable for various indoor testing environments. Internally, it features an automatic dual-power switching circuit. When only one power supply is available, the load is automatically 100% applied to the current circuit. When both power supplies are restored, the load is automatically distributed 50% to each power supply.

This dual-circuit load cell is equipped with comprehensive protection logic, including overvoltage protection, overcurrent protection, overload protection, current imbalance protection, temperature protection, and communication interruption protection. It supports local/remote operation and monitoring switching, and also supports parallel control of multiple load cells (1+N). It is widely applicable to performance testing of power systems, UPS, generator sets, air conditioning systems, and other equipment in data centers.

Resource Download:

Main Parameters

Rated Parameters of the Power Supply Under Test

AC400V/50~60Hz/3P5W+ AC400V/50~60Hz/3P5W;

Rated Load Power

21kW (total rated power of dual circuits);

Load Characteristics

Resistive Load;

Load Connection Mode

Star connection + delta connection;

Loading Accuracy

±3%

Three-phase Balance

≤3%

Load Regulation Capability

0-21kW adjustable, minimum step 1kW;

Load Protection Function

Over-temperature protection, overvoltage protection, overcurrent protection, etc.

Load Control

Manual load step switching via circuit breakers

Load Working Mode

Continuous Operation;

Cooling Method

Air Cooling

Operation Method

Touch Screen Local Control; or Remote Control Via Host Computer;

Measurement and Control Function

Touch screen control, measuring the voltage, current, power, frequency, etc. of the power supply under test;

Load expansion

Parallel expansion of 1+N load units;

Operating Environment

Indoor type; Temperature Range -10℃ to +55℃;

External Dimensions

485×1850×605mm (W×H×D, Enclosure);

Weight

138kg

Operating Altitude

≤2000 Meters

Installation and Transportation

Enclosure with load-bearing lifting holes and casters

Insulation Class

F;

Product Application Scope

Suitable for data center power supply testing and air conditioning system testing.

Features

  • Supports local/remote control switching. Local control is operated via a local touchscreen, suitable for single load cells or small-scale, ready-to-test applications. Remote control is suitable for multi-load cell control testing scenarios and supports integration with other load cell models for testing.


  • Networking is simple. Multiple devices can be cascaded via wired connections, or a wireless router can be deployed in the test area to configure a wireless network. Networking can be quickly set up according to testing needs for multi-device control testing.


  • With load cell control software, centralized monitoring and control of load cells, as well as recording, processing, and analysis of test data, can be quickly achieved.


  • Supports centralized control of up to 800 load cells.


  • Load cells can be used in parallel, offering convenient and reliable operation.


  • Capable of performing sudden load increases and decreases in power ranges from 0 to 21kW;


  • Minimum step unit: 1kW;


  • Supports automatic switching between dual power supplies. When powered by a single circuit, the load is automatically 100% applied to the current circuit. When dual power supplies are restored, the load is automatically distributed 50% to each power supply.


  • Real-time display and recording of various electrical parameters (current, voltage, frequency, power, etc.) during load testing;


  • Test data can be exported to a CSV file.


  • Uses resistance tubes with low temperature coefficients and low impedance. The casing is made of stainless steel tubing resistant to salt spray and acids/alkalis, ensuring long-term continuous operation;


  • Accuracy during loading and unloading tests: ±3%, higher accuracy than other resistive loads;


  • Equipped with overvoltage/current protection, overload protection, phase loss protection, current imbalance protection, temperature protection, and communication interruption protection, ensuring long-term reliability of the load;

Rack Mounted Doual Source Load Bank Customization Services

Protection threshold parameter customization

Default Configuration: Overvoltage alarm 241V / error 244V, overcurrent alarm 32A / error 34A, overtemperature alarm 55℃ / error 60℃, etc., are factory fixed. Customization Notes: Alarm and error protection thresholds at each level can be customized and adjusted according to the rated parameters of the power supply under test and the requirements of the test scenario, within the allowable parameter range of the equipment (e.g., overvoltage 185-250V, overcurrent 0-34A), to adapt to test requirements with different voltage levels and different protection sensitivities.

Dual-channel power distribution ratio customization

Default configuration: When powered by dual power supply, the total load power is distributed evenly at a ratio of 50%:50%. Customization instructions: The power distribution ratio of the dual power supply can be customized according to the capacity difference of the user's dual power supply (such as 60%:40%, 70%:30%, etc.) to meet the test scenario requirements of asymmetrical power supply systems and heterogeneous backup power supplies.

Input interface and cable customization

Default configuration: Standard configuration includes a 32A European standard 5-pin male and female plug, cable length of 5 meters, and wire diameter of 6mm². Customization notes: It can be customized to replace the input plug with different standards such as Chinese standard and American standard, adjust the cable length, or upgrade the cable protection level to adapt to the power distribution standards and on-site wiring distances of different countries and regions.

Cooling system parameter customization

Default configuration: Minimum airflow threshold 3000 CFM, airflow adjustment step 250 CFM, using 10 sets of speed-adjustable fans. Customization notes: The minimum airflow limit and fan speed control logic can be adjusted according to the test environment temperature and load duty cycle requirements, or the fan specifications can be upgraded to improve heat dissipation redundancy in high-temperature environments and ensure the stability of continuous high-load operation.

Customization of enclosure appearance and structure

Default configuration: Gray orange-textured case, dimensions 485×1850×605mm, standard configuration includes 4 lifting rings and casters with brakes. Customization notes: Case color and surface treatment can be customized, case size and installation structure can be adjusted (such as rack mounting or fixed mounting), and casters, lifting rings and other handling accessories can be added or removed to adapt to the installation and placement needs of different sites.

Communication and Protocol Customization

Default configuration: Supports wired cascading and wireless LAN networking, with dedicated host computer control software. Customization notes: Can be customized to adapt to common industrial communication protocols such as Modbus RTU/TCP and SNMP, and interface with the user's existing monitoring system, or custom-developed dedicated data interaction interfaces to achieve deep linkage with the user's automated testing system.

Load power and stepper customization

Default configuration: Total rated power 21kW, minimum power step 1kW, 0-21kW continuously adjustable. Customization notes: The total rated power capacity can be adjusted according to the user's testing needs, or the minimum power step level can be modified (such as 0.5kW step) to improve the adjustment accuracy of the low power range and adapt to refined testing scenarios.

Environmental Adaptability Customization

Default configuration: Indoor type, operating temperature -10℃~+55℃, altitude ≤2000 meters. Customization notes: It can be customized and upgraded to special versions such as outdoor rainproof type, high altitude adaptable type, and strong salt spray corrosion resistant type. The selection of components and protective structure can be adjusted to meet the testing needs of special environments such as outdoor construction sites, coastal areas, and high altitude sites.

Customization of software UI, multi-languages ​​and special functions

1. UI Customization: Customize the software splash screen, color scheme, and brand logo; adjust layout and settings to adapt to different screen resolutions.

2. Multilingual Pack Customization: Customize for multiple languages ​​including English, French, German, and Arabic.

3. Special Function Customization: Customize exclusive functional modules, such as custom tiered loading, exception alarm methods, automatic recording and backtracking of operation logs, etc.

FAQ

The equipment features a built-in dual-power automatic switching controller and PLC control logic. With dual power supplies operating normally, the total load is automatically distributed evenly between Port A and Port B at a 50%-50% ratio. If one power supply suddenly fails, the entire load automatically switches to the normal power supply circuit within milliseconds, requiring no manual intervention. When power is restored to the failed circuit, the PLC controls the load to be redistributed evenly between the two circuits. This seamless switching ensures the continuity of testing for the backup power supply and dual-power system.

Supports 1+N parallel expansion mode; a single host computer (host computer) can control up to 800 load banks of various types via our remote control software. Different models of load banks are also compatible for joint control. Networking methods support wired and wireless networking. Wired networking can be cascaded via network cables through the device's built-in two communication interfaces. Wireless networking allows load banks to be grouped and connected to a wireless router, and then the host computer connects to the wireless router for centralized management of all connected load banks.

Our dual-circuit air-cooled load cell is designed with a loading accuracy of ±3% and a three-phase current balance of ≤3%, which is better than the average level of conventional resistive load cells.

  • When a warning (such as overvoltage, undervoltage, or overcurrent alarm) is triggered, the equipment will continue operating as a warning only.

 

  • When an error (such as overvoltage, overcurrent, emergency stop, communication interruption, or overtemperature fault) is triggered, the equipment will trigger a protective shutdown. An alarm will sound, and the alarm information will be simultaneously pushed to the host computer (control computer) to prompt manual intervention.

 

  • The fault status will be latched. After the fault is cleared, the equipment can be manually reset by clicking the "Clear Alarm" button on the HMI's STATUS interface to resume normal operation.

To ensure efficient heat dissipation, especially for air-cooled load cells, there should be no obstructions within 1 meter in front of the front and side air inlets, and no obstacles or other equipment within 5 meters of the air outlets. This will prevent hot air recirculation and overheating of the equipment. After the load is unloaded, the fan will continue to run for a period of time according to the program settings to remove residual heat from the equipment (especially resistors). It will only stop when the temperature drops to a safe threshold. Do not turn off the power before the fan stops.

Local/remote control modes can be easily operated via the local touchscreen HMI. On the Home screen, clicking the green "local" button switches to local operation, while clicking the green "remote" button switches to remote operation from the host computer.

 

In remote control mode, multiple units can be centrally loaded and unloaded, and voltage, current, power, frequency, imbalance, etc., can be monitored in real time. Data is automatically recorded to the host computer and can be exported as a CSV table for subsequent analysis, meeting the needs of large-scale system-level testing scenarios.

The resistance tube is made of U-shaped nickel-chromium alloy, and the outer shell is made of stainless steel alloy tube resistant to salt spray and acids and alkalis. It has the characteristics of low temperature coefficient and stable impedance, which can ensure consistent performance during long-term continuous operation. 


The product has an insulation class of F and is equipped with dual temperature protection for over-temperature of the resistance area and the electrical control area. With the stepless speed-regulating air cooling system, it can support long-term continuous operation.

  1. Check if there is undervoltage on either of the tested power supplies. If the voltage value is lower than the undervoltage alarm threshold (factory default 200V), it will affect the switching logic.

 

  1. Check the meter communication status. If the meter communication is interrupted for more than 16 seconds, it will cause abnormal voltage detection, thus preventing automatic switching from being triggered.

This load cell is designed for indoor use, with an operating temperature range of -10℃ to +55℃ and an altitude not exceeding 2000 meters. It should be used and stored in a dry, well-ventilated indoor environment, avoiding water exposure, moisture, and extreme temperatures. Although the casing is resistant to salt spray and acid/alkali corrosion, long-term storage in such environments is still recommended.