Main Parameters
|
Rated Power |
AC230V/50~60Hz |
|---|---|
|
Power Supply Interface Under Test |
Terminal Block |
|
Rated Power of The Load |
3kW |
|
Load Steps |
0.5kW, 0.5kW, 1kW, 1kW |
|
Load Characteristics |
Resistive Load |
|
Loading Accuracy |
±3% |
|
Three-Phase Balance |
≤3% |
|
Load Regulation Capability |
Adjustable from 0 to 3kW, with a minimum step of 0.5kW |
|
Load Power Factor |
1.0 |
|
Load Protection Function |
Over-temperature protection, overvoltage protection, overcurrent protection, etc. |
|
Load Control |
Manual load step switching via circuit breakers |
|
Load Working Mode |
Continuous Operation |
|
Cooling Method |
Forced Air Cooling |
|
Operation Mode |
Local Control |
|
Load Expansion |
Parallel expansion of 1+N load units |
|
Operating Environment |
Indoor Type |
|
Operating Ambient Temperature |
Range: -10°C to +55°C |
|
External Dimensions |
430×350×130mm (L×W×H, cabinet); reference dimensions, customizable |
|
Ref. Weight |
18kg |
|
Box Color |
Gray painted finish / customizable |
|
Operating Altitude |
≤2000m |
|
Insulation Class |
F |
|
Product Application Scope |
Suitable for performance testing of power supply systems, UPS systems, generator sets, and other equipment in data centers |
Feature
-
Built for continuous load testing and heat load simulation. It runs stably at full power for long periods. Compact and easy to operate, ideal for production-line burn-in, rack thermal testing and on-site continuous load verification.
-
High-temperature resistant, high-precision alloy resistor rods and industrial switches. Built-in over-temperature auto shutoff for safe 7×24 continuous full-load operation without performance drop.
-
Long-life EC fans with an isolated front-in / rear-out airflow path. Heat exits through the rear of the rack — no hot air blown toward the front panel or recirculated.
-
Standard industrial power connector; no software setup or complicated tuning needed. After power-on, just flip the front-panel breakers to add load in steps. Real-time current is shown clearly on the digital display.
-
Slim 3U all-metal chassis (430 × 350 × 130 mm) saves space. Front and rear handles plus standard 19-inch rack ears are included. Mount it in a rack or carry it easily to the production line or test site — tough and impact-resistant.
Rack Mounted Load Bank Customization Services
Custom Power Ratings
Customize single-unit rated power from 3kW up to 10kW to match your specific continuous burn-in, thermal simulation, and load testing requirements.
Custom AC/DC Voltage
Available in custom AC voltages (110V–380V, 50/60Hz) or DC configurations to match regional power grids and different power supply tests.
Custom Load Steps
Customize physical breaker step combinations (such as 100W, 200W, 500W, or 750W steps) to achieve the exact load gradient needed for your test routine.
Custom Airflow & Terminals
Configure airflow direction (front-to-rear or front-to-top exhaust) and power connectors (NEMA/CEE/Schuko plugs, Anderson connectors, or bolt clamps) to fit site layouts.
Custom Chassis Dimensions
Adjust enclosure depth and rack height (2U, 3U, or 4U) to fit shallow cabinets, standard 19-inch server racks, or compact production benches.
Custom OEM Branding
Customize front-panel silk-screening, rating nameplates, enclosure paint finishes, and brand logos for system integrators, rental fleets, and OEM partners.
FAQ
No —— The load bank series built for tough, long load tests and heat simulation, not for precision lab measurement. It’s made to last and costs less — great for power supply burn-in and server rack heat testing.
Flip the front breakers; 500W per step, no software needed.
It has built-in over-temperature auto shutoff. If the temperature goes too high — blocked airflow or hot room — the load cuts off automatically, so your other rack gear stays safe.
It can run unattended. Built-in over-temperature auto shutoff protects the unit and nearby equipment during long tests.
Yes. If the terminals in the photos or the parameters in the spec sheet do not match your needs, you can contact us directly for a custom configuration.