Main Parameters
|
Rated Parameters of The Power Supply Under Test |
AC400V/50~60Hz |
|---|---|
|
Power Supply Interface Under Test |
AC Socket 3P+N+E |
|
Rated Power of The Load |
21kW |
|
Load Steps |
0.5kW, 0.5kW, 1kW, 2kW, 3kW, 3kW, 5kW, 5kW |
|
Load Characteristics |
Resistive Load |
|
Loading Accuracy |
±3% |
|
Three-Phase Balance |
≤3% |
|
Load Regulation Capability |
Adjustable from 0 to 20kW, with a minimum step of 0.5kW |
|
Load Power Factor |
1.0 |
|
Load Protection Function |
Over-temperature protection, overvoltage protection, overcurrent protection, etc. |
|
Load Control |
Manual load step switching via circuit breakers |
|
Load Working Mode |
Continuous Operation |
|
Cooling Method |
Forced Air Cooling |
|
Operation Mode |
Local Control |
|
Load Expansion |
Parallel expansion of 1+N load units |
|
Operating Environment |
Indoor Type |
|
Operating Ambient Temperature |
Range: -10°C to +55°C |
|
External Dimensions |
485×1850×605mm (W×H×D, cabinet); reference dimensions, customizable |
|
Ref. Weight |
138kg |
|
Box Color |
Gray painted finish / customizable |
|
Operating Altitude |
≤2000m |
|
Insulation Class |
F |
|
Product Application Scope |
Suitable for performance testing of power supply systems, UPS systems, generator sets, and other equipment in data centers |
Feature
-
Built with high-precision alloy resistor tubes that offer low temperature drift and excellent heat resistance, ensuring stable operation at full load even in harsh environments.
-
Features a multi-generation optimized airflow design that quickly removes heat generated during operation and supports extended continuous use.
-
Equipped with over-temperature protection for safe operation in unattended applications.
-
The mobile design allows for easy transport and rapid deployment.
Rack Mounted Liquid cooled Load Bank Customization Services
Rated Power & Loading Step Customization
Adjust the single-unit rated power and customize the minimum loading step to meet requirements of fine graded loading tests.
Input Voltage & Incoming Terminal Customization
Input voltage (single/three-phase) and incoming terminal type (bolt-clamp, busbar or socket) are configurable to match site grid and wiring.
HMI & Host Software Customization
RS485, Modbus, host computer remote control, parallel linkage and dual power supply switching logic are configurable.
Structure Size & Mounting Customization
Rack height, internal layout and cable entry direction can be tailored for standard rack or cabinet header installation.
Protection & Sensor Configuration Customization
Temperature, flow, pressure and leak detection sensors, alarm thresholds and interlock protection functions can be added or removed as required.
Appearance & Marking Customization
Cabinet paint finish, caster wheels and lifting eyes are available; nameplate and OEM branding can be customized.
FAQ
The 21kW unit is not available as an integrated cabinet-type product. If you need a cabinet-type 21kW load bank, we can customize a solution for you: 19-inch rack-mount load modules installed in a mobile rack cabinet with casters, delivering 21kW total.